Features
features
DVM S Water
Model Name
model_name
AM100MXWANR/EU
Power Supply (Outdoor Unit) [Φ, #, V, Hz]
power_supply_outdoor_unit___v_hz
3,4,380-415,50/60
System
system
HEAT RECOVERY
Performance (nominal)
performance_nominal
10 HP
Capacity
capacity
28.0 kW
95,500 Btu/h
31.5 kW
107,500 Btu/h
Power Input
power_input
4.87 kW
5.04 kW
Current Input
current_input
7.8 A
8.1 A
Power
power
16.1 A
20.0 A
Energy Efficiency
energy_efficiency
5.8
6.3
Compressor
compressor
Inverter Scroll
5.18 kW
DS-GB052FAVB
PVE
1100 cc
Piping Connections
piping_connections
9.52 mm
3/8
22.22 mm
7/8
32A mm
19.05 mm
3/4
170(190) m
50(40) m
PT 1/2
Refrigerant
refrigerant
R410A(Fluorinated greenhouse gas, GWP=2,088)
5.80 kg
12.11 tCO2e
Sound
sound
48 dBA
70.0 dBA
External Dimension (Outdoor Unit)
external_dimension_outdoor_unit
160.0 kg
167.0 kg
770 x 1,000 x 545 mm
840 x 1,200 x 620 mm
Operating Temp. Range
operating_temp_range
10 ~ 45 ℃
10 ~ 45 ℃
Water Side Heat Exchanger
water_side_heat_exchanger
PHE (Plate Heat Exchanger)
1 EA
96.0 LPM
30.00 kPa
1.96 Mpa
PT1-1/4 A
Subscribe to our newsletter to receive the latest product innovations, updates, and much more.
Reach out to our sales team to ask any questions you may have and discuss the best options for your business.