Features
features
DVM S Water
Model Name
model_name
AM100MXWANR/EU
Power Supply (Outdoor Unit) [Φ, #, V, Hz]
power_supply_outdoor_unit___v_hz
3,4,380-415,50/60
System
system
HEAT RECOVERY
Performance (nominal)
performance_nominal
10 HP
Capacity
capacity
28.0 kW
31.5 kW
Power Input
power_input
4.87 kW
5.04 kW
Current Input
current_input
7.8 A
8.1 A
Power
power
16.1 A
20.0 A
Energy Efficiency
energy_efficiency
5.8
6.3
Piping Connections
piping_connections
9.52 mm
3/8
22.22 mm
7/8
32A mm
19.05 mm
3/4
170(190) m
50(40) m
PT 1/2
Refrigerant
refrigerant
R410A(Fluorinated greenhouse gas, GWP=2,088)
5.80 kg
12.11 tCO2e
Sound
sound
48 dBA
70.0 dBA
External Dimension (Outdoor Unit)
external_dimension_outdoor_unit
160.0 kg
770 x 1,000 x 545 mm
Operating Temp. Range
operating_temp_range
10 ~ 45 ℃
10 ~ 45 ℃
Water Side Heat Exchanger
water_side_heat_exchanger
PHE (Plate Heat Exchanger)
1 EA
96.0 LPM
30.00 kPa
1.96 Mpa
PT1-1/4 A
Subscribe to our newsletter to receive the latest product innovations, updates, and much more.