Features
features
DVM S Water
Model Name
model_name
AM080MXWANR/EU
Power Supply (Outdoor Unit) [Φ, #, V, Hz]
power_supply_outdoor_unit___v_hz
3,4,380-415,50/60
System
system
HEAT RECOVERY
Performance (nominal)
performance_nominal
8 HP
Capacity
capacity
22.4 kW
25.2 kW
Power Input
power_input
3.67 kW
3.97 kW
Current Input
current_input
5.9 A
6.4 A
Power
power
16.1 A
20.0 A
Energy Efficiency
energy_efficiency
6.1
6.4
Piping Connections
piping_connections
9.52 mm
3/8
19.05 mm
3/4
32A mm
15.88 mm
5/8
170(190) m
50(40) m
PT 1/2
Refrigerant
refrigerant
R410A(Fluorinated greenhouse gas, GWP=2,088)
5.50 kg
11.48 tCO2e
Sound
sound
48 dBA
70.0 dBA
External Dimension (Outdoor Unit)
external_dimension_outdoor_unit
160.0 kg
770 x 1,000 x 545 mm
Operating Temp. Range
operating_temp_range
10 ~ 45 ℃
10 ~ 45 ℃
Water Side Heat Exchanger
water_side_heat_exchanger
PHE (Plate Heat Exchanger)
1 EA
80.0 LPM
22.00 kPa
1.96 Mpa
PT1-1/4 A
Subscribe to our newsletter to receive the latest product innovations, updates, and much more.
Reach out to our sales team to ask any questions you may have and discuss the best options for your business.